Brand | TrippLite |
UPS Type | Rack |
Nominal Power VA | 3KVA |
Delivery time | 6 días hábiles |
Warranty | 12 meses |
Protects connected mission-critical equipment against damage, downtime, and data loss due to blackouts, brownouts, surges, and line noise. It converts the input AC power into filtered DC power and then returns it to AC power with a pure sine wave.
Input Phase: Single phase.
Specified input current (Maximum Load): 24A.
Nominal Input Voltage(s) Supported: 120V AC.
UPS input connection type: L5-30P.
Input breakers: No.
UPS Power Cord Length (ft): 5.
UPS Power Cable Length (m): 3.5.
Recommended Electrical Service: 30A 120V.
Output Capacity (VA): 3000.
Output Capacity (kVA): 3.
Output Capacity (Watts): 2700.
Output Capacity (kW): 2.7.
Output Capacity Details: INVERTER SHORT CIRCUIT PROTECTION: The inverter short circuit protection is electrically protected; SURCHARGE CAPACITY: Supports inverter operation of up to 105% continuous load, 125% load for 30 seconds; 150% load for 10 seconds and >150% load for 0.5 seconds before switching to BYPASS (when the input voltage and frequency to the bypass are WITHIN the bypass limits of 120V ±10%) or OFF (when the shunt input voltage or frequency is OUTSIDE the shunt limits of 120V ±10%).
Output Voltage Regulation (Line Mode) : +/- 2%.
Output voltage regulation (battery mode): +/- 2%.
Outlets with Load Management: Two switchable load banks with three outlets.
Outlet Breakers: Two 20 A breakers protect 3 5-15/20R outlets; The L5-30R outlet cannot be connected to switches.
Output AC Waveform (AC Mode): Pure sine wave).
Output AC Waveform (Battery Mode): Pure Sine Wave.
Nominal Output Voltage(s) Supported: 100V; 110V; 115V; 120V; 127V.
Outlets: (6) 5-15/20R; (1) L5-30R.
Individually Controllable Load Banks: Yes.
Battery Type: Valve Regulated Lead Acid [VRLA].
Autonomy at Full Load (min): 4.8.
Autonomy at Half Load (min): 13.8.
Expandable Autonomy: Yes.
Expandable Battery Life: Supports extended operation with external battery modules.
External battery module compatibility: BP72V15-2U (limit 1); BP72V28RT-3U (multi-module compatible); BP72V18-2US (multi-module compatible).
System DC voltage (VDC): 72.
Battery Recharge Rate (Batteries Included): Less than 8.1 hours from 10% to 90% (typical, discharge to full charge).
UPS Type: Rack.
Measurements (WxHxD): 60 x 24x 76 cm.
Weight: 40kg